Temperature and pressure relief valve for solar wa
Temperature And Pressure Relief Valve For Solar Water Heater ( A K E Make )
Minimum Order Quantity: 1 Piece
Product Brochure
Valve Size | up to 3.0 inch, up to 3.0 inch |
Material | Brass |
Finish Type | Bronze |
Size | 1/2" & 3/4" |
Brand | A K E |
Media | Air |
Pressure | 3 KD,5 KG,7 KG,9 KG AVILABALE |
End Connection | 1/2" & 3/4" |
Tank Material | Copper |
Rust Resistance | Yes |
Model Number | WYA-15 & WYA-20 |
I Deal In | New Only |
Capacity | 0-10 litres |
Power | 0-2 (KW) |
Temperature & Pressure Relief Valve
Designed and checked Based on American “ANSI Z21.22” Standard.
Using MethodTemperature and Pressure Relief Valves is suitable for Installing at the Pressurized solar water heater, gas heater, electric water heater , water heater of fuel, heat pump water heater , sensitive function heater, etc. various kinds of heaters( such as the boiler) and hot water containers . The valve will be opened at the set temperature and pressure to protect the water tank.
Technical Parameter
•Set Pressure(Psi): 75,87,100,125,150psi (0.50.60.70.81.0MPa)
•Set Pressure Tolerance: +5%,-10% of the set pressure.
•Set Temperature: From 65 to99. (As you’re required)
•Set Temperature Tolerance: 99-5; other set Temperature is ±5PS: We can made different type of valves as you’re required.
•Dimensions/WeightsHow to Installation
•Temperature and Pressure Relief Valves should be installed on the top of the water heater top or side. The Temperature sensing element must be immersed in the water within the top 6″of the tank.
•The eliminating pipeline should be installed under the relief valve. Its terminal station distance in floor drain should be greater than 6″to make it easily remove and observe water
Direct Installed on the Top Direct Installed in the Side
How to Safeguard And Maintenance:
•After installing water heater the users must lift the relief valve handle once at least every year, so as to ensure that unblocked things in the waterway of the relief valve.
•Before operating handles, please check the elimination pipeline which joining the relief valve, guaranteed that the hot water from the relief valve discharge the proper place, otherwise it may cause the bodily injury.
•If the handle is lifted, without water flowing out, it proves that the relief valve is invalid. Then it should turn off the water heater immediately and check the valve.
Temperature & Pressure Relief Valve For Solar Water Heater ( A K E Make )
Minimum Order Quantity: 1 Piece
Product Brochure
Valve Size | up to 3.0 inch |
Capacity | 0-10 litres |
Brand | A K E MAKE |
Media | Fuel, Gas, Air, Water |
Body Material | BRONZ |
Tank Material | Brass |
Usage/Application | Hotels |
Max Rated Pressure | 3 bar, 10-15 Bar, 0-5 Bar, 5-10 Bar |
Temperature and pressure relief valve for solar water heater
Temperature & Pressure Relief Valve
AKE Combination Temperature and Pressure Relief Valves are designed for the protection of water heaters and storage tanks. WYA-20 meet ANSI Z21.22.
WYA-20 Valves are completely automatic and reseat after either temperature or pressure relief. They are offered in 3/4" sizes with male inlets and female outlets.
Performance:
- Available Set Pressures :150 psi standard.
- Temperature Relief: 210°F standard.
- Service: Hot Water.
- Body: Bronze
- Internal Parts: Brass and stainless steel
- Seat Disc: Silicone
- Pressure Spring: Stainless steel
Designed and checked Based on American “ANSI Z21.22” Standard.
Ⅰ、Using MethodTemperature and Pressure Relief Valves is suitable for Installing at the Pressurized solar water heater, gas heater, electric water heater , water heater of fuel, heat pump water heater , sensitive function heater, etc. various kinds of heaters( such as the boiler) and hot water containers . The valve will be opened at the set temperature and pressure to protect the water tank.
Ⅱ、Technical Parameter
•Set Pressure(Psi): 75,87,100,125,150psi (0.5、0.6、0.7、0.8、1.0MPa)
•Set Pressure Tolerance: +5%,-10% of the set pressure.
•Set Temperature: From 65℃ to99℃. (As you’re required)
•Set Temperature Tolerance: 99℃-5℃; other set Temperature is ±5℃
PS: We can made different type of valves as you’re required.
•Dimensions/Weights
Ⅲ、How to Installation
•Temperature and Pressure Relief Valves should be installed on the top of the water heater top or side. The Temperature sensing element must be immersed in the water within the top 6″of the tank.
•The eliminating pipeline should be installed under the relief valve. Its terminal station distance in floor drain should be greater than 6″to make it easily remove and observe water
Direct Installed on the Top Direct Installed in the Side
Ⅳ、How to Safeguard And Maintenance:
•After installing water heater the users must lift the relief valve handle once at least every year, so as to ensure that unblocked things in the waterway of the relief valve.
•Before operating handles, please check the elimination pipeline which joining the relief valve, guaranteed that the hot water from the relief valve discharge the proper place, otherwise it may cause the bodily injury.
•If the handle is lifted, without water flowing out, it proves that the relief valve is invalid. Then it should turn off the water heater immediately and check the valve.
Temperature Pressure Relief Valve For Solar Water Heater A K E Make
Minimum Order Quantity: 1 Piece
Product Brochure
Valve Size | up to 3.0 inch |
Capacity | 0-10 litres |
Brand | A K E make |
Color | BRASS |
Type Of Collector | Integral Collector (Batch System) |
I Deal In | New Only |
Model Name/Number | WYA-15,20 |
Usage/Application | Solar water Heater |
Max Rated Pressure | 0-5 Bar |
Temperature & Pressure Relief Valve
Temperature & Pressure Relief Valve (WYA-15)
Designed and checked Based on American “ANSI Z21.22” Standard.
โ
ใUsing MethodTemperature and Pressure Relief Valves is suitable for Installing at the Pressurized solar water heater, gas heater, electric water heater , water heater of fuel, heat pump water heater , sensitive function heater, etc. various kinds of heaters( such as the boiler) and hot water containers . The valve will be opened at the set temperature and pressure to protect the water tank.
โ
กใTechnical Parameter
•Set Pressure(Psi): 75,87,100,125,150psi (0.5ใ0.6ใ0.7ใ0.8ใ1.0MPa)
•Set Pressure Tolerance: +5%,-10% of the set pressure.
•Set Temperature: From 65โ to99โ. (As you’re required)
•Set Temperature Tolerance: 99โ-5โ; other set Temperature is ±5โ
PS: We can made different type of valves as you’re required.
•Dimensions/Weights
โ
ขใHow to Installation
•Temperature and Pressure Relief Valves should be installed on the top of the water heater top or side. The Temperature sensing element must be immersed in the water within the top 6″of the tank.
•The eliminating pipeline should be installed under the relief valve. Its terminal station distance in floor drain should be greater than 6″to make it easily remove and observe water
Direct Installed on the Top Direct Installed in the Side
โ
ฃใHow to Safeguard And Maintenance:
•After installing water heater the users must lift the relief valve handle once at least every year, so as to ensure that unblocked things in the waterway of the relief valve.
•Before operating handles, please check the elimination pipeline which joining the relief valve, guaranteed that the hot water from the relief valve discharge the proper place, otherwise it may cause the bodily injury.
•If the handle is lifted, without water flowing out, it proves that the relief valve is invalid. Then it should turn off the water heater immediately and check the valve.
Pressure Relief Valves For Solar Water Heater ( A K E Make )
Minimum Order Quantity: 1 Piece
Valve Size | 1/2",3/4" |
Material | Brass/Bronze |
Capacity | 10-25 litres |
Brand | A K E |
Media | Water |
Pressure | 1MPA UP TO 10 MPA, 1MPA UP TO 10 MPA |
Tank Material | Brass |
Max Rated Pressure | 0-5 Bar |
Pressure Relief Valves A K E Make
·Designed and checked Based on American ANSI Z 21.22 Relief valve. ·GB/T 21384-2009 Standard. Ⅰ、 Using Method: Pressure Relief Valves is suitable for Installing at the Pressurized solar water heater, gas heater, electric heater, water heater for fuel, water heater of heat pump, sensitive function heater,etc.various kinds of heaters, air and supply hot system of reduce pressure device, can lower the temperature and reduce pressure automaticallyⅡ、
.Technical Parameter: ·Set Pressure:(Mpa):0.1、0.3、0.5、0.6、0.7、0.8、1.0 ·Set Pressure Tolerance: +5%,-10% of the set pressure. ·Max Working Temperature: 110℃ ·Max Working Pressure: 1Mpa. PS: We can made different type of valves as you’re required. Dimensions/Weights: Ⅲ 、
How to Installation ·The Valve can be installed horizontally or vertically, not upside down, to prevent The accumulation of impurities affects the normal work; ·The outlet must be grounded drain valve leakage, ensure that the atmosphere can Be observed drainage; ·Drain should make antifreeze leak, kept clear in order to avoid damage to material and personnel. Ⅳ、How to Safeguard And Maintenance: ·After installing water heater the users must lift the relief valve handle once at least half year, so as to ensure that unblocked things in the waterway of the relief valve. ·Before operating handles, please check the elimination pipeline which joining the relief valve, guaranteed that the hot water from the relief valve discharge the proper place, otherwise it may cause the bodily injury. ·If the handle is lifted, without water flowing out, it proves that the relief valve is invalid. Then it should turn off the water heater immediately and check the valve. Ⅴ、
Warranty time:12 Months.
Model Inlet X Outlet in High mm Wide mm Weight g Mark YA-15 R1/2×Rp1/2 83 41 180 YA-20 R3/4×Rp3/4 83 42 195 YA-15A R1/2×Rp1/2 70 41 127 (Plastic Red Handle) YA-15C R1/2×Rp1/2 63 40 127 (Stainless steel Handle) YA-15D Rp1/2×M8 68 43 125 ( Plastic Red Handle ) YA-15N Rp1/2×Rp1/2 68 41 130 YA-15E Rp1/2×M9 68 44 125 ( Plastic Red Handle )